CM-P3 Fire Alarm Control Panel
Products
CM-P3 Fire Alarm Control Panel
Back to List
Product Feature
Product Specification
Certificate
Download
Comprehensive circuit monitoring and corresponding indicators: each circuit is equipped with monitoring functions on fire, circuit break and short circuit, respectively
The fire alarm circuit and the indicator circuit are able to detect circuit break and offer protection against short circuit
The system always keeps close watch over battery charging and the voltage of the stand-by battery to ensure that the central control unit functions well in all circumstances to prevent any disaster
Each circuit is equipped with a testing button to ensure the normal function of each monitoring circuit
Key-controlled function switches
prevent false alarms caused by accidental touch
Digital detection of voltage error: whenever a voltage error is detected by the system, an error alarm will sound and an indicator will light on
The system is equipped with a
two-stage accumulation function
to prevent false alarms. When the detector activates for the first time, the system will automatically reset the detector. If another signal is received later, the system will then confirm that there is a fire, for fear of a false alarm
“Self-Protection” mode and “Non Self-Protection” mode
are available to fire alarms
Separate control switches: separate control panels for main audio, local audio, indicators, and reporting output
There is a “Not-Located” indicator above each switch
Digital-electronic switches are used due to advantages of dust proofing and a long service life
A control panel with all necessary master indicators: the status of system alarm, power supply quality, and circuit connection are shown
The alarm buzzer sounds in a loud voice: personnel in charge will be informed immediately in case of a firm alarm
A large fire indicator: in case of a fire, a fire alarm will sound and the large fire indicator will flash
SPECIFICATION
MODEL NO.
CM-P3
POWER SUPPLY
240V AC 50/60 Hz ± 10%
STANDBY BATTERY
24V DC / Lead-Acid (Non-Spillable) Battery
E.O.L RESISTOR
10 KΩ
EXTERNAL CIRCUIT
To-and -fro below 50 Ω
NO. OF BELLS
1 time of panel circuits
CHARGING VOLTAGE & CIRCUIT
26V DC below 450mA, Trickle Charging
CURRENT VOLTAGE
24V DC operation voltage, below 5V 32mA
CHARGING CURRENT
26.4V DC, under 450mA, Trickle Charge
DETECTORS
No limit of R.O.R or Fixed Temp. Heat Detector can be installed; Each circuit can connect to a maximum of 20 smoke detectors (standby current for detector: 24V DC 25 μA below).
NO. OF INDICATORS
1 time of panels circuits
CASE MATERIAL
Standard Material of 1.2mm
REPORT CONTACT
No voltage N.O. contact
Capacity 250V AC 7A × 2 sets
ORDER INFORMATION
CM-P3-1L
FACP 01 zone with battery
CM-P3-2L
FACP 02 zone with battery
CM-P3-4L
FACP 04 zone with battery
CM-P3-8L
FACP 08 zone with battery
CM-P3-12L
FACP 12 zone with battery
CM-P3-16L
FACP 16 zone with battery
CM-P3-24L
FACP 24 zone with battery
EXTERNAL DIMENSIONS
MODEL
Wall Mounting Type
CIRCUIT NO.
1L/2L/4L/8L
12L/16L
24L
H (mm)
400
495
580
W (mm)
300
300
300
D (mm)
120
120
120
Inquiry